Description
circuit breaker VL1600 UL type PG (cat no. NPX3A160) non-interchangeable frame, with circuit breaker approval acc. to UL 489 standard breaking capacity 3-pole; NEMA rating 35kA/480V and 25kA/600V (molded case circuit breaker) trip unit LCD ETU, LI/LS/LSI TA=40°C In=1600A, rated current ISD=1.25-10xIR, II=6xIN short-circuit protection IR=700-1600A overcurrent rel. for line protection without auxiliary release without auxiliary/alarm switch